Yokogawa EJA118A Differential Pressure TransmitterYokogawa EJA118A Differential Pressure Transmitter
SPECIFICATIONS1. 0.065 % High accuracy. Yokogawa Pressure Transmitter EJA118
Model EJA118W, EJA118N and EJA118Y
Diaphragm Sealed Differential Pressure Transmitters
1. Diaphragm seals are used to prevent process medium form entering directly into the pressure-sensing assembly of the differential pressure transmitter, they are connected to the transmitter using capillaries filled with fill fluid. 2. Model EJA118W, EJA118N and EJA118Y Diaphragm Sealed Differential Pressure Transmitters can be used to measure liquid, gas, or steam flow, as well as liquid level, density, and pressure. 3. They output a 4 to 20 mA DC signal corresponding to the measured pressure differential. The transmitters also feature remote setup and monitoring through communications with the model BT200/100 BRAIN TERMINAL, CENTUM CS/XL system etc.
Features:
1. Output Signal “0”: 4 to 20 mA DC, 2-wire system with digital communication
2. Failure Alarm:
Output status at CPU failure and hardware error;
Up-scale:110%, 21.6 mA DC or more(standard) Down-scale: -5%, 3.2 mA DC or less
-2.5%, 3.6 mA DC or less (Optional code /F1)
Note: Applicable for Output signal code D and E
3. Supply Voltage “0”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code /A)
10.5 to 30 V DC for intrinsically safe, Type n, nonincendive, or non-sparking type
10.5 to 28 V DC for TIIS intrinsically safe type
4. Process Temperature Limits:
(See ‘Optional Specifications’ for Explosion-protected types)
5. Ambient Humidity Limits:
5 to 100 % R.H.(at 40 oC)
Model and suffix codes:
|